Short answer
Ideal Evomax 2 boilers show numbered faults from 1 to 99 (for example 'Fault 39 — lockout flow overheat'), not L or F codes. Each fault is a warning (W), blocking (B — clears itself when the condition goes) or lockout (L — needs a manual reset). Codes 1–24 are sensor faults, 30–42 temperature supervision, 50–81 flame, fan and water flow, and 93–99 internal control faults.
How faults appear on the Evomax 2
When a fault occurs the status display title bar alternates with the word 'Fault'. Turning the scroll knob shows the detail, such as 'Fault 39'. Once the cause is fixed the fault is reset by pressing reset in that display. Several faults at once are listed together and each can be opened.
Ideal's user guide also notes that a blocked or frozen condensate pipe makes the boiler gurgle and then lock out showing 'Ignition Lockout', and that an overheat shows 'Overheat Lockout'.
The faults we see most in London plant rooms
Fault 58 (no flame after restarts) and 52–56 (flame loss) usually trace to low gas inlet pressure under load, a worn ignition/ionisation electrode, a blocked condensate trap or flue recirculation. Faults 50, 67, 70 and 78 point to water flow — pumps, valves, dirty strainers or poor system design on cascades. Faults 39–42 are overheats that are almost always a flow problem rather than a boiler fault.
Before you reset
A single reset after a power cut or a known one-off event is reasonable. Repeated resets are not: many commercial controls count resets and lock out further (for example a 'too many resets' code), and resetting a flame or gas valve fault over and over can mask a dangerous condition. If a lockout returns, isolate the appliance and call a Gas Safe registered engineer with the relevant commercial competence.
Ideal Evomax 2 fault code list
| Code | Meaning | What to check |
|---|---|---|
| 1 | Flow thermistor open circuit (blocking) | — |
| 2 | Flow thermistor short circuit (blocking) | — |
| 3 | Return thermistor open circuit (blocking) | — |
| 4 | Return thermistor short circuit (blocking/warning) | — |
| 5 | Flue thermistor open circuit (blocking/warning) | — |
| 6 | Flue thermistor short circuit (blocking) | — |
| 7 | DHW thermistor open circuit (warning) | — |
| 8 | DHW thermistor short circuit (warning) | — |
| 9 | Outside thermistor defect, open or short (warning) | — |
| 10 | Water pressure sensor defect (blocking) | — |
| 11 | Flow thermistor open circuit (lockout after 24h) | — |
| 12 | Flow thermistor short circuit (lockout after 24h) | — |
| 13 | Return thermistor open circuit (lockout after 24h) | — |
| 14 | Return thermistor short circuit (lockout after 24h) | — |
| 15 | Flue thermistor open circuit (lockout after 24h) | — |
| 16 | Flue thermistor short circuit (lockout after 24h) | — |
| 17 | Heat thermistor open circuit (lockout after 24h) | — |
| 18 | Heat thermistor short circuit (lockout after 24h) | — |
| 19 | Heat thermistor open circuit (blocking) | — |
| 20 | Heat thermistor short circuit (blocking) | — |
| 21 | Header thermistor open circuit (warning) | — |
| 22 | Header thermistor short circuit (warning) | — |
| 23 | Room (hc1) thermistor open circuit (warning) | — |
| 24 | Room (hc1) thermistor short circuit (warning) | — |
| 30 | Blocking due to flow overheat | — |
| 31 | Blocking due to return overheat | — |
| 32 | Blocking due to flue overheat | — |
| 33 | Flow and return reversed (blocking) | — |
| 34 | Thermistor pipe fit supervision active (blocking) | — |
| 35 | Thermistor pipe fit supervision (lockout) | — |
| 36 | Flow gradient supervision (blocking) | — |
| 37 | Flue gradient supervision (reserved) | — |
| 38 | Blocking delta temperature flow/return | — |
| 39 | Lockout flow overheat | — |
| 40 | Lockout return overheat | — |
| 41 | Lockout flue overheat (flue thermistor) / lockout thermal fuse | — |
| 42 | Blocking due to heat exchanger overheat | — |
| 50 | Blocking due to no CH water flow | — |
| 51 | Low water pressure (blocking) | — |
| 52 | No flame signal at start — restart (warning) | — |
| 53 | Flame loss during operation — endless restarts (warning) | — |
| 54 | Flame loss during operation — lockout after restart attempts used | — |
| 55 | Flame loss during stabilisation — restart attempts (warning) | — |
| 56 | Flame loss during stabilisation — lockout after restart attempts used | — |
| 57 | False flame with heat demand (lockout) | — |
| 58 | No flame after restarts (lockout) | — |
| 59 | Fan speed, stand-still check (blocking/lockout) | — |
| 60 | Fan speed not achieved, e.g. pre-purge or post-purge test (lockout) | — |
| 61 | Error fan speed during pre-purge — 5 restarts then lockout | — |
| 62 | Error min/max supervision fan speed during operation — restart (warning) | — |
| 63 | Mains overvoltage (warning) | — |
| 64 | Mains undervoltage (blocking) | — |
| 65 | OpenTherm plus communication error (warning) | — |
| 66 | Too many remote resets (lockout) | — |
| 67 | No water flow indication (blocking) | — |
| 68 | PWM pump blocking error (blocking) | — |
| 69 | PWM pump electrical error (blocking) | — |
| 70 | Heat exchanger water flow below minimum (blocking) | — |
| 71 | PWM pump dry run error (blocking) | — |
| 72 | Warning code from pump (blocking) | — |
| 73 | VariCAN error (warning) | — |
| 74 | Safety interlock function activated — controlled shutdown (blocking) | — |
| 75 | Air pressure switch error (lockout) | — |
| 76 | Air pressure switch warning — restart | — |
| 77 | High water pressure (blocking) | — |
| 78 | Minimum water flow rate (blocking/lockout) | — |
| 79 | Maximum water flow rate exceeded (warning) | — |
| 80 | Quartz crystal error (warning) | — |
| 81 | 0–10V input out of range (blocking) | — |
| 93 | Retails supervision error (lockout) | — |
| 94 | Request for re-update (lockout) | — |
| 95 | Blocking due to programming mode | — |
| 96 | Lockout parameter mismatch | — |
| 97 | Lockout parameter set | — |
| 98 | Internal blocking error | — |
| 99 | System lockout (internal lockout error) | — |
Source: Ideal Commercial Boilers — Evomax 2 User Guide (219417). Codes and meanings can differ between versions and control software — always check the manual for your exact appliance.