Andrews MAXXflo Water Heater Fault Codes

Short answer

Andrews MAXXflo water heaters show A codes for lockouts (reset with the reset button once fixed) and E codes for blocking faults (which need a repair before they clear). A01 is three failed ignitions, A02 an overheat with no water flow, A24 too many flame failures, and E41 live and neutral reversed.

Multiple burner modules

The display alternates the letter and the burner module number. With faults on more than one module it cycles every 5 seconds, and reset only clears the module currently shown.

Before you reset

A single reset after a power cut or a known one-off event is reasonable. Repeated resets are not: many commercial controls count resets and lock out further (for example a 'too many resets' code), and resetting a flame or gas valve fault over and over can mask a dangerous condition. If a lockout returns, isolate the appliance and call a Gas Safe registered engineer with the relevant commercial competence.

Andrews MAXXflo fault codes

CodeMeaningWhat to check
A01Three failed ignitions — still no flame detected after three ignitions—
A02Overheat stat failure — no water flow, flow sensor not detecting a temperature rise—
A03The two flow sensors differ by more than 10°C for more than 60 seconds—
A05Gas valve relay error — relay not switching correctly—
A06Safety relay error — relay not switching correctly—
A08Fan error — fan not reaching target speed for more than 60 seconds—
A09Control error: internal storage location—
A10Stored parameter contents not correct—
A11Flow temperature went above 95°C—
A12Stored contents do not match the software version—
A14–A19Control error: internal storage location—
A20Flame still present 10 seconds after the gas valve has closed—
A21Flame detected before the gas valve opened during start-up—
A24Too many flame failures — flame failed three times in one burn cycle—
E0Read error: not able to read stored parameters (slave board)—
E09Control error: internal RAM location not correct—
E12Incorrect parameters programmed in the slave board—
E13–E16Control error: AD-circuit reference measurement out of range—
E18Control error: internal RAM—
E19Control error: not able to read parameters—
E20No slave board present—
E22Power fault: 50 Hz supply deviation too large—
E28–E31Control error: AD-circuit reference measurement (slave board)—
E33Flame detected when gas valve was closed—
E41Phase error: live and neutral reversed—
E42Phase error: supply frequency deviation too large—
E44Control error: poor communication between the two processors—
E47Return sensor open circuit—
E48Flow sensor open circuit—
E60Tank sensor open circuit—
E63Return sensor short circuit—
E64Flow sensor short circuit—
E65Return sensor open circuit (master board)—
E70Tank sensor shorted—
E75Return sensor shorted—
E78Reset error: too many user resets—

Source: Andrews MAXXflo installation manual (2016). Codes and meanings can differ between versions and control software — always check the manual for your exact appliance.

Figures are typical for UK natural gas. The current edition of the relevant IGEM standard and the manufacturer's instructions always take precedence on site.