Hamworthy Fault Codes: Purewell VariHeat, Fleet, Stratton mk1, Wessex ModuMax mk2

Short answer

Older Hamworthy boilers with Siemens LMU controls — Purewell VariHeat c and he, Fleet, Stratton mk1 and Wessex ModuMax mk2/HE — use their own fault list. The most common are 133 (no flame at end of safety time), 128 and 134 (flame lost during operation), 132 (safety shutdown), 110/111 (limit thermostat) and 118 (water pressure too low).

Lockout and internal codes

On LMU boilers a lockout code flashes with an alarm symbol (for example E150). Hamworthy's manual explains that pressing both line selection buttons for 3 seconds shows the internal error code (for example 238). Note both before resetting.

What usually causes them

These are older boilers, so worn flame probes, tired gas valves, perished seals and fouled heat exchangers are common. Code 129 (fan speed outside limits) often means a failing fan bearing. Repeated 133s on a cold morning are frequently low inlet pressure when the whole plant fires together.

Before you reset

A single reset after a power cut or a known one-off event is reasonable. Repeated resets are not: many commercial controls count resets and lock out further (for example a 'too many resets' code), and resetting a flame or gas valve fault over and over can mask a dangerous condition. If a lockout returns, isolate the appliance and call a Gas Safe registered engineer with the relevant commercial competence.

Hamworthy LMU control fault codes

CodeMeaningWhat to check
10Fault outside sensorCheck connection, check sensor, check cable.
28Fault flue gas sensorCheck connection, check sensor, check cable.
32Fault flow temperature sensor 2Check connection, check sensor, check cable.
50Fault DHW temperature sensor 1Check connection, check sensor, check cable.
52Fault DHW temperature sensor 2Check connection, check sensor, check cable.
61Fault room unit 1Check room device.
62Wrong room unit 1 or wrong radio clock connectedConnect compatible room control unit.
77Fault air pressure sensorCheck connection, check sensor, check cable.
78Fault water pressure sensorCheck connection, check sensor, check cable.
82Address collision on LPBCheck addresses of connected modules.
91Data overflow in EEPROMHardware fault, LMU may need replacing.
92Hardware fault in electronicsHardware fault, LMU may need replacing.
95Invalid time of daySet correct time.
1002 clock time mastersCheck settings of LMU, only 1 master allowed.
105Maintenance messageP629 to reset : change from 0 to 1.
110Limit thermostat has cut outAllow the boiler to cool and reset thermostat, investigate cause of overheating.
111Limit thermostat has cut outAllow the boiler to cool and reset thermostat, investigate cause of overheating.
113Flue gas supervision equipment has cut outCheck the cause of high flue gas temperature. Check sensor.
117Water pressure too highCheck system pressure, check water pressure sensor
118Water pressure too lowCheck system pressure, check water pressure sensor
119Water pressure switch has cut outCheck water pressure.
128Loss of flame during operationCheck connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.
129Fan speed maximum/minimum has been violatedCheck fan.
130Flue gas limit temperature exceededCheck the cause of high flue gas temperature. Check sensor.
132Safety shutdownCheck gas pressure. Check flue & condensate trap for blockages. Check safety switches.
133No flame on completion of safety timeCheck operation of gas valve. Check spark igniter.
134Loss of flame during operationCheck connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.
140Inadmissible LPB segment number/device N°Check settings of LMU and boiler address settings.
148Incompatibility LPB... interface / basic unitCheck settings of LMU
151Internal fault with LMUCheck connections to clip in, replace module, check LMU.
152Fault in connection with LMU settingsCheck LMU settings.
153LMU has locked outPress reset button (code appears if reset button is pressed when there are no faults).
154Flow ProblemsCheck water flow through the boiler & check the pumps.
160Fan speed threshold not reachedCheck obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris.
161Maximum fan speed exceededCheck parameters.
162Fault air pressure switch (does not close)Check air pressure switch and cable and connections.
164Fault heating circuit flow switch / pressure switchCheck air pressure switch and cable and connections.
166Fault air pressure switch (does not open)Check air pressure switch and cable and connections.
180Chimney sweep function activeCheck boiler operation setting.
181Controller stop function activeCheck boiler operation setting.
183LMU in parameter setting modeUnit in programme mode.

Source: Hamworthy Heating — fault code tool. Codes and meanings can differ between versions and control software — always check the manual for your exact appliance.

Figures are typical for UK natural gas. The current edition of the relevant IGEM standard and the manufacturer's instructions always take precedence on site.